Rectangular fire damper with a fire resistance up to 120 minutes, available in the largest dimensions (including battery assembly up to 2450x1650 mm).
- Large dimensions.
- Many options and variants.
- Battery assembly tested in rigid wall.
- Model available for use in potentially explosive atmospheres.
CU2+CFTH : Rectangular fire damper CU2 with the unlocking mechanism CFTH. It automatically unlatches the damper blade when the temperature in the duct rises above 72ºC. due to the rise in temperature the fusible link melts. This causes an armed internal torsion spring to unwind and thereby release the damper blade into its safety position (closed). The fusible link must be replaced after functioning.
the damper can be unlocked manually to test the proper functioning of the mechanism. The damper must be reset manually.
CU2+ONET24 FDCU : Spring return actuator with fusible link + unipolar beginning-and end-of-range switch- 24V
CU2+ONET24 ST FDCU : Spring return actuator with fusible link + unipolar beginning- and end-of-range switch and plug (ST). 24V
CU2+ONET230 FDCU : Spring return actuator with fusible link + unipolar beginning- and end-of-range switch 230V